Home  »  Middle voltage power cables  »  2XSE( FL)2Y A2XSE(FL)2Y

2XSE( FL)2Y A2XSE(FL)2Y

Uo/U - 20/35 kV  IEC 60502-2
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal and radial water-blocking ele­ments, are designed for transfer and distribution of electrical power with nominal voltage Uo/U20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
 
Cable construction
Construction
According to IEC 60502
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound
Water resisting element
Layer of semi-conductive water absorbing tapes - discret
Metal screen
Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm
Water resisting element
Layer of semi-conductive water absorbing tapes
Cable assembly
Three insulated and screened phases with longitudinal water-blocking element are twisted in three core cable
Filling - filiers with water-blocking element
Inner sheath
Radial
protection from moisture ingress
Layer of semi-conductive water absorbing tapes
Al foil with copolymer layer
Sheath
PE compound - HDPE
Color
Black
Technical data
Conductor resistance at 20°C
According to BDS904 (IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
20/35 kV
Highest system voltage Um,
no more than
20/35 kV
 
42 kV
Test voltage Uo/U
AC ( ) - 5 min
DC ( ) - 15 min
20/35 kV
70 kV
224 kV
Level of partial discharge
at 2*Uo
Bending radius, min
Temperature of laying
max. 5 pC
 
 
15x D cable
no less than -5°C
Temperature of
exploitation
Tests
Force of strain in laying
N max.
where:
-30 to 500C according to IEC 60502 Al cores - 30*n*S core Cu cores - 50*n*S core n- number of cores and-S-cross-section in mm
 
Construction data 2XSE(FL)2Y, A2XSE(FL)2Y    20/35 kV
Number of conductors and nominal cross sec­tion
Thickness of insula­tion
 
 
Thickness
of
sheath
Nominal cross sec­tion of screen
Cable diameter approx.
 
 
 2XSE(FL)2Y
A2XSE(FL)2Y
Mass of
Cu approx.
Mass of
cable
approx.
Mass of
Al approx.
Mass of
cable
approx.
Nxmm2
mm
mm
mm
mm
kg/km
kg/km
kg/km
kg/km
20/35 kV
 
 
 
 
 
 
 
 
3x70 rm /25
8.8
3.5
25
49.7
1965
5665
585
4285
3x95 rm /25
8.8
3.7
25
83.6
2730
6730
810
4810
3x120 rm /25 3x150rm /25
8.8
8.8
3.8
3.9
25
25
87.2
90.1
3440 4245
7530
8775
1025
1255
5295
5785
3x185 rm /35
8.8
4.0
35
94.0
5310
10195
1575
6465
3x185 rm /50
8.8
4.0
50
94.0
5310
10334
1575
6595
3x240 rm /25
8.8
4.2
25
79,6
6980
12285
2070
7375