Home  »  Middle voltage power cables  »  2XSE(F)2YB2Y / 2XSE( F)2YBY A2XSE( F)2YB2Y/ A2XSE(F)2YBY

2XSE(F)2YB2Y / 2XSE( F)2YBY A2XSE( F)2YB2Y/ A2XSE(F)2YBY

Uo/U - 6/10, 12/20 kV IEC 60502-2
The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements ,are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 12/20kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Cable construction
Construction
according to IEC 60502 -2
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound
Water resisting element
Layer of semi-conductive water absorbing tapes - discret
Metal screen over each phase
Cu wires concentrically laid and    one contact of Cu tape with thickness of 0.1mm
Water resisting element
Layer of semi-conductive water absorbing tapes
Cable assembly
Three insulated and screened phases with longitudinal water-blocking element are twisted in three core cable
Inner sheatth / bedding /
Filling and inner sheath-PE - LDPE
Armour
two steel tapes
or two steel galvanized tapes
Sheath
For type 2Y- PE compound -
HDPE
For type Y- PVC compound
type ST2 according to IEC 60502
Color
For type 2Y - black For type Y - red
Technical data
Conductor resistance at 20°C
According to BDS904 (IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C    /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage Uo/U, no more than
6/10; 12/20 kV
12kV; 24kV kV
Test voltage Uo/U
AC (≈) - 5 min
DC (=) - 15 min
6/10; 12/20 kV
15kV; 30kV kV
48kV; 96kV kV
Level of partial discharge
at 2*Uo
Bending radius, min
Temperature of laying
max. 5 pC
 
 
15x D cable
no less than - 20°C
Temperature of exploitation
-30 to 50°C
Tests
according to IEC 60502-2 or DIN VDE 0276-620
Force of strain in laying N max.
where:
Al cores - 30*n*S core Cu cores - 50*n*S core n- number of cores and -S-cross-section of conductors in mm
 
Construction data 2XSE(F)2YB2Y, A2XSE(F)2YB2Y6/10; 12/20kV
Number of conductors and nominal cross sec­tion
Thickness of insula­tion
Thickness
of
sheath
Nominal cross sec­tion of screen
Cable diameter approx.
 
2XSE(F)2YB2Y
A2XSE(F)2YB2Y
Mass of
Cu approx.
Mass of
cable
approx.
Mass of
Al approx.
Mass of
cable
approx.
Nxmm2
mm
mm
 mm2
mm
kg/km
kg/km
kg/km
kg/km
6/10 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3,4
2.7
16
53.0
1010
3635
295
2920
3x50 rm /16
3,4
2.7
16
55.5
1360
4190
405
3240
3x70 rm /16
3,4
2,9
16
59.5
1965
5090
585
3710
3x95 rm /16
3,4
2,9
16
62.5
2730
6100
805
4175
3x120rm /25 3x150rm /25
3,4
3,4
3,1
3,2
25
25
67.0
70.5
3440 4245
7215
8330
1020
1255
4800
5340
3x185rm /25 3x240rm /25
3,4
3,4
3,4
3,6
25
25
74.5
80.0
5310 6980
9780
11995
1575
2070
6040
7085
12/20 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3x50 rm /16
5.5
5.5
2.9
3,0
16
16
61.0
63.5
1010 1360
4430
5040
295
405
3720
4085
3x70 rm /16
3x95 rm /16
5.5
5.5
3.1
3.3
16
16
67.0
71.0
1965 2730
5975
7125
585
805
4595
5195
3x120rm /25
5.5
3.4
25
75.0
3440
8190
1020
5770
3x150rm /25
5.5
3,5
25
78.0
4245
9330
1255
6340
3x185rm /25
5.5
3,6
25
82.0
5310
10805
1575
7070
3x240rm /25
5.5
3,8
25
87.5
6980
13070
2070
8160
6/10 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3,4
2.7
16
53.0
1010
3850
295
3135
3x50 rm /16
3,4
2.7
16
55.5
1360
4425
405
3470
3x70 rm /16
3x95 rm /16
3,4
3,4
2,9
2,9
16
16
59.5
62.5
1965 2730
5355
6380
585
805
3975
4455
3x120rm /25
3,4
3,1
25
67.0
3440
7540
1020
5120
3x150rm /25
3,4
3,2
25
70.5
4245
8685
1255
5690
3x185rm /25
3x240rm /25
3,4
3,4
3,4
3,6
25
25
74.5
80.0
5310 6980
10160
12435
1575
2070
6425
7525
12/20 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3x50 rm /16
5.5
5.5
2.9
3.0
16
16
61.0
63.5
1010 1360
4710
5330
295
405
3995
4375
3x70 rm /16
5.5
3.1
16
67.0
1965
6300
585
4920
3x95 rm /16
5.5
3.3
16
71.0
2730
7480
805
5555
3x120rm /25
3x150rm /25
5.5
5.5
3.4
3.5
25
25
75.0
78.0
3440 4245
8580
9750
1020
1255
6160
6760
3x185rm /25
5.5
3,6
25
82.0
5310
11260
1575
7525
3x240rm /25
5.5
3,8
25
87.5
6980
13575
2070
8670