Home  »  Middle voltage power cables  »  2XSEY A2XSEY

2XSEY A2XSEY

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kV
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV to 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Cable construction
Construction
According to IEC 60502
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound
Metal screen
Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase
Cable assembly
Three insulated and screenesd phases are twisted with fillings and tape support
Inner sheath
PVC compound
Sheath
PVC compound
type ST2 according to IEC 60502
Color
red
Technical data
Conductor resistance at 20°C
According to BDS904
(IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C    /100h per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage
6/10; 12/20 kV
Uo/U, no more than
12kV; 24kV kV
Test voltage Uo/U
6/10; 12/20 kV
AC () - 5 min
15kV; 30kV kV
DC (=) - 15 min
48kV; 96kV kV
Level of partial discharge at 2*Uo
 max. 5 pC
Bending radius, min
15x D cable
Temperature of laying
no less than - 20°C
Temperature of
exploitation
 -30 to 50°C
 Tests
 
according to IEC 60502-2 or DIN VDE 0276-620
Force of strain in laying N where:
 
 
Al cores - 30*n*S core Cu cores - 50*n*S core
n- number of cores and -S-cross-section of
conductors in mm
 
Construction data 2XSEY, A2XSEY 3.6/6; 8.7/15; 20/35 kV 
Number of conductors and nominal cross sec­tion
Thickness of insula­tion
Thickness
of
sheath
Nominal    Cab cross sec­tion of
screen
Cable diameter approx.
 
2XSEY
A2XSEY
Mass of
Cu approx.
Mass of
cable
approx.
Mass of
Al approx.
Mass of
cable
approx.
Nxmm2
mm
mm
 mm2
mm
kg/km
kg/km
kg/km
kg/km
3,6/6 kV
 
 
 
 
 
 
 
 
3x35 rm /16
2,5
2,5
16
46,2
1010
2609
298
1933
3x50 rm /16
2,5
2,5
16
48,8
1363
3079
404
2168
3x70 rm /16
2,5
2,5
16
53,0
1968
3904
584
2590
3x95 rm /16
2,5
2,7
16
57,1
2732
4914
809
3087
3x120rm /16 3x150rm /25
2,5
2,5
2,8
2,9
16
25
60,3
64,2
3440 4245
5784
6943
1023
1257
3488
4105
3x185rm /25 3x240rm /25
2,5
2,6
3,0
25
25
68,5
74,3
5311 6981
8268
10332
1579
2071
4722
5668
3x300rm /25
2,8
3,4
25
79,6
8661
12497
2589
6729
 
 
 
 
 
 
 
 
 
8,7/15 kV
3x35 rm /16
 
4 5
 
2,6
 
16
 
56,5
 
1010
 
3365
 
298
 
2689
3x50 rm /16 3x70 rm /16
4,5
4,5
2,7
2,8
16
16
59,3
63,3
1363 1968
3883
4760
404
584
2972
3446
3x95 rm /16
4,5
3,0
16
67,2
2732
5844
809
4017
3x120rm /16
4,5
3,1
16
70,6
3440
6751
1023
4456
3x150rm /25
4,5
3,2
25
74,7
4245
7978
1257
5140
3x185rm /25
4,5
3,4
25
78,6
5311
9386
1579
5840
3x240rm /25 3x300rm /25
4,5
4,5
3,5
3,7
25
25
84,3
79,6
6981 8661
11502
13631
2071
2589
6838
7863
 
 
 
 
 
 
 
 
 
20/35 kV
 
 
 
 
 
 
 
 
3x50 rm /16
8,8
3,4
16
75,6
1363
6077
404
5166
3x70 rm /16
8,8
3,5
16
79,6
1968
7083
584
5769
3x95 rm /16 3x120rm /16
8,8
8,8
3,7
3,8
16
16
83,7
87,1
2732 3440
8284
9343
809
1023
6456
7054
3x150rm /25
8,8
3,9
25
91,0
4245
10724
1257
7885