Home  »  Middle voltage power cables  »  2XSEYB2Y A2XSEYB2Y

2XSEYB2Y A2XSEYB2Y

Uo/U  -  3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV to 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Cable construction
Construction
according to IEC 60502 -2
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound
Metal screen over each phase Metal screen
-I option - Cu tapes laid with overlap over each phase -II option - Cu wires laid concen trically
Cable assembly
Three insulated and screened phases are twisted with fillings and tape support
Inner sheatth
PVC compound
Armour
two steel tapes
or two steel galvanized tapes
Sheath
PE compound
type ST7 according to IEC 60502
Color
Black
Technical data
Conductor resistance at 20°C
According to BDS904 (IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C   /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage Uo/U, no more than
6/10; 12/20 kV 12kV; 24kV kV
Test voltage Uo/U
AC (≈) - 5 min
DC (=) - 15 min
6/10; 12/20 kV
15kV; 30kV kV
48kV; 96kV kV
Level of partial discharge
at 2*Uo
Bending radius, min
Temperature of laying
max. 5 pC 
 
 
15x D cable
no less than - 20°C
Temperature of exploitation
-30 to 50°C
Tests
according to IEC 60502-2 or DIN VDE 0276-620
Force of strain in laying N max.
where:
Al cores - 30*n*S core Cu cores - 50*n*S core n- number of cores and -S-cross-section of conductors in mm
 
 
Construction data 2XSEYB2Y, A2XSEYB2Y   6/10; 12/20; 18/30 kV
Number of conductors and nominal cross sec­tion
Thickness of insula­tion
Thickness
of
sheath
Nominal cross sec­tion of screen
Cable diameter approx.

 
2XSEYB2Y
A2XSEYB2Y
Mass of
Cu approx.
Mass of
cable
approx.
Mass of
Al approx.
Mass of
cable
approx.
Nxmm2
mm
mm
 mm2
mm
kg/km
kg/km
kg/km
kg/km
6/10 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3,4
2,5
16
48,4
1010
3579
298
2903
3x50 rm /16
34
2,6
16
51,0
1363
4137
404
3226
3x70 rm /16
3x95 rm /16
3,4
34
2,7
2,9
16
16
55,0
59 3
1968 2732
5043
6153
584
809
3729
4327
3x120rm /16
3x150rm /25
3,4
3,4
3,0
3,1
16
25
62,5
66,4
3440 4245
7085
8330
1023
1257
4782
5492
3x185rm /25
3,4
3,2
25
70,5
5311
9718
1579
6172
3x240rm /25
3,4
3,4
25
76,3
6981
11871
2071
7207
3x300rm /25
3,4
3,7
25
83,2
8661
14868
2589
9101
 
 
 
 
 
 
 
 
 
12/20 kV
3x35 rm /16
 
5.5
 
2,8
 
16
 
57.2
 
1010
 
4149
 
298
 
3437
3x50 rm /16
5.5
2.9
16
60.0
1363
4733
404
3773
3x70 rm /16
5.5
3.0
16
64.0
1968
5668
584
4284
3x95 rm /16
5.5
3,2
16
68.0
2732
6792
809
4869
3x120 rm /16
5.5
3,3
16
71.5
3440
7800
1023
5384
3x150rm /25
3x185 rm /25
5.5
5.5
3,4
3,5
25
25
75.0
80.0
4245 5311
8916 11123
1257
1579
5928
7391
3x240 rm /25 5.5 3,7 25 85.5 6981 13404 2071 8494
18/30 kV
 
 
 
 
 
 
 
 
3x35 rm /16
8.0
3.2
16
69.5
1010
5583
298
4871
3x50 rm /16
3x70 rm /16
8.0
8.0
3.3
3.4
16
16
72.5
76.1
1363 1968
6220
7226
404
584
5261
5842
3x95 rm /16
3x120 rm /16
8.0
8.0
3,6
3,7
16
16
80.2
83.5
2732 3440
8424
9497
809
1023
6501
7080
3x150rm /25
8.0
3,8
25
87.0
4245
10672
1257
7684
3x185 rm /25
8.0
4,0
25
92.3
5311
13075
1579
9343