Home  »  Middle voltage power cables  »  2XSEYBY A2XSEYBY

2XSEYBY A2XSEYBY

Uo/U - 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
 
Cable construction
Construction
according to IEC 60502 -2
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound
Metal screen over each phase Metal screen
-I option - Cu tapes laid with over
lap over each phase
-II option - Cu wires laid concen
trically
Cable assembly
Three insulated and screened phases are twisted with fillings and tape support
Inner sheatth
PVC compound
Armour
two steel tapes
or two steel galvanized tapes
Sheath
PVC compound
type ST2 according to IEC 60502
Color
red
Technical data
Conductor resistance at 20°C
According to BDS904
(IEC60228) class 2
Operating temperature
90°C continuous operation
 
Overload temperature
130°C  /100h per year max./
Short circuit temperature
250°C  /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage
6/10; 12/20 kV
Uo/U, no more than
12kV; 24kV kV
Test voltage Uo/U
6/10; 12/20 kV
AC () - 5 min
15kV; 30kV kV
DC (=) - 15 min
48kV; 96kV kV
Level of partial discharge
at 2*Uo
 max. 5 pC
Bending radius, min
15x D cable
Temperature of laying
no less than - 20°C
Temperature of
exploitation
 -30 to 50°C
 Tetsts
 
according to IEC 60502-2 or DIN VDE 0276-620
Force of strain in laying N where:
 
 
Al cores - 30*n*S core Cu cores - 50*n*S core
n- number of cores and -S-cross-section of
conductors in mm
 
Construction data 2XSEYBY, A2XSEYBY   6.10; 12/20; 18/30 kV 
Number of conductors and nominal cross sec­tion
Thickness of insula­tion
Thickness
of
sheath
Nominal    Cab cross sec­tion of
Cable diameter approx.
 2XSEYBY
A2XSEYBY
Mass of
Cu approx.
Mass of
cable
approx.
Mass of
Al
approx.

Mass of
cable
approx.
screen
 
Nxmm2
mm
mm
 mm2
mm
kg/km
kg/km
kg/km
kg/km
6/10 kV
 
 
 
 
 
 
 
 
3x35 rm /16
3,4
2,5
16
48,4
1010
3639
298
2963
3x50 rm /16
3,4
2,6
16
51,0
1363
4203
404
3292
3x70 rm /16
3x95 rm /16
3,4
3,4
2,7
2,9
16
16
55,0
59,3
1968 2732
5117
6239
584
809
3803
4412
3x120rm /16 3x150rm /25
3,4
3,4
3,0
3,1
16
25
62,5
66,4
3440 4245
7178
8433
1023
1257
4882
5595
3x185rm /25
3,4
3,2
25
70,5
5311
9831
1579
6285
3x240rm /25
3,4
3,4
25
76,3
6981
12001
2071
7337
3x300rm /25
3,4
3,7
25
83,2
8661
15023
2589
9255
 
 
 
 
 
 
 
 
 
12/20 kV
3x35 rm /16
 
5,5
 
2,9
 
16
 
58,7
 
1010
 
4717
 
298
 
4041
3x50 rm /16
5,5
2,9
16
61,3
1363
5286
404
4376
3x70 rm /16
5,5
3,1
16
65,5
1968
6281
584
4967
3x95 rm /16
5,5
3,2
16
69,4
2732
7433
809
5606
3x120rm /16
5,5
3,3
16
72,8
3440
8430
1023
6134
3x150rm /25 3x185rm /25
5,5
5,5
3,4
3,6
25
25
76,7
82,0
4245 5311
9756
12065
1257
1579
6918
8519
3x240rm /25   3,8 25 87,7 6981 14364 2071 9700
18/30 kV
 
 
 
 
 
 
 
 
3x50 rm /16
8,0
3,3
16
73,7
1363
6765
404
5854
3x70 rm /16
8,0
3,5
16
78,0
1968
7852
584
6538
3x95 rm /16
8,0
3,7
16
83,4
2732
9914
809
8086
3x120rm /16 3x150rm /25
8,0
8,0
3,8
3,9
16
25
86,7
90,5
3440 4245
10996
12462
1023
1257
8701
9623