Home  »  Middle voltage power cables  »  2XSY A2XSY

2XSY A2XSY

Uo/U - 3.6/6 kV, 8.7/15 kV, 20/35 kVIEC 60502-2
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV and 20/35 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Cable construction
Construction
According to IEC 60502
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound
Metal screen
Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm.
Separating layer
Layer of plastic tape
Sheath
PVC compound
type ST2 according to IEC 60502
Color
red
Technical data
Conductor resistance at
According to BDS904
20°C
(IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage
6/10; 12/20 kV
Uo/U, no more than
12kV; 24kV kV
Test voltage Uo/U
6/10; 12/20 kV
AC () - 5 min
15kV; 30kV kV
DC (=) - 15 min
48kV; 96kV kV
Level of partial discharge at 2*Uo
 
max. 5 pC
Bending radius, min
15x D cable
Temperature of laying
no less than - 20°C
Temperature of
exploitation
 -30 to 50°C
 Tests
 
according to IEC 60502-2 or DIN VDE 0276-620
Force of strain in laying N max.
where:
 
Al cores - 30*n*S core Cu cores - 50*n*S core
n- number of cores and -S-cross-section of conductors in mm